![]() |
![]() |
| OPERATION MANUAL | Adobe Acrobat File for Operation Manual ( 101kb ) |
Description The EMS547 Controller is a microprocessor based engine controller with built-in service reminder features. It will automatically warn you when certain service items need to be performed and will signal your engine to shut down if a fault is detected. The system is accessed through three push-buttons and a back-lit, dot-matrix liquid crystal display. A more detailed description of operator functions can be found in the operating instruction section. The system will have the capability to communicate with a remote terminal, via modem communications. The user will be able to view the state and status of the controller from the remote terminal. The controller will call the remote terminal if a failure occurs. |
| Sensor Inputs The EMS Controller accepts several different types of sensor inputs. Below is a list of which types are accepted. See the wiring hookup drawing for terminal details. Electric Gauge Senders. These inputs allow you to use standard electric gauge type senders for pressure and temperature. Digital alarm inputs. These inputs are negative grounding type inputs. Typically, external shutdown switches are wired to these inputs. They can include vibration, low pressures, high temperatures, and low levels. Frequency input. This input is an optically isolated speed sensing input. You may get your speed signal from either a magnetic pickup or the tachometer post of your alternator. |
| Outputs The EMS547 controller has a total of seven (7) open collector transistor outputs. One (1) of these can be selected as a watchdog output. All outputs are rated for 200 ma. |
| Operating the EMS Controller The EMS Controller is very simple to operate. Once the Setup numbers have been configured for your operation, the unit will automatically perform its duties with very little user interface. The front plate has three push-buttons for scrolling through information, changing set-points, and acknowledging alarms. See the Operating Instructions section for more information. |
| CONTROL SEQUENCE OUTLINE |
| START SEQUENCE |
Control panel selector in
"AUTO" position. If there are no failures, [STATUS: SELECTOR -AUTO; STATE: PANEL
READY].
When the VENT FAN DELAY expires, the vent fan is signaled to stop and the following shutdown circuits are "ARMED" immediately,
NOTE: CYCLE CRANKING. If the engine does not start on the first crank, the controller will de-energize the fuel valve and starter outputs for the entire rest cycle. NOTE: OVERCRANK. If the engine fails to start after the field-programmable number (preset to 6) of cranking attempts, OVERCRANK will be indicated on the alpha-numeric display. The Micro-controller Start Sequence will be halted and automatic control circuits will be locked out. The lockout must be manually reset before normal operation may be resumed. The MURPHYMATIC® Micro-controller will close ENGINE FAILURE status contacts. The "Fail" Status is reset when the panel is reset by moving the panel selector to the "OFF" position.
|
STOP SEQUENCE
|
Special Features
Communications Set-Up
Remote Terminal Communication Port Set-Up.
Password: The monitor has a S# for password setup. By using l Ù Ú keys the user can enter the password. This password is used two (2) ways.
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
| Operating the Interface |
| By using the three push-buttons and the liquid crystal display, you can make set-point changes, acknowledge alarms, and scroll through the display. The graphic below shows the display and push-buttons. The l Ù Ú keys are membrane type push-buttons. The l button is best described as an Enter key. You can confirm a set-point and acknowledge alarms with this button. The Ù button is used for increasing a set-point or scrolling up the display. The Ú button is used for decreasing a set-point or scrolling down the display. The 2 line dot-matrix liquid crystal display shows information pertinent to its current running mode. |
|
| For example, if the unit receives a remote start signal, it will auto start the engine and display the current operation on the screen. These states include Crank On, Crank Off, Warm-up, Cooldown, etc. When the unit has brought the engine on stream, the display will scroll vertically through the engine vital signs. These include, Oil Pressure, Engine Temperature, Engine Speed, Running Hours, etc. |
| First Time Setup | ||||||
Before using the unit for the first time, it is necessary
to configure all the set-points. To access the S-numbers (Setup numbers), use the
following procedure:
To change an S-number, the following procedure should be used. We will change the DAY OF WEEK set-point for this example.
|
| MAIN DISPLAYS During normal operation, the unit allows you to scroll through a number of informative front displays by using the Ù Ú buttons. A listing and explanation of each follows:
|
| S-Number Description and Listing The S-numbers are used for customizing the controller to your specific application. Included in the S-numbers are the adjustable variables for the system. These S-Numbers must be set before trying to use the unit. Following is a list of available S-Numbers and a short description of the function of each. See Secret Code Supplement for the entry code number. The factory defaults in this write are configured by the factory. They are for a starting point for configuration of the unit to meet your application. Refer to the Polar Power supplemental information for the set points as set by Polar Power.
|
S-0: |
Manual 'EXIT' from the S-number setup mode. Press " 'CIRCLE' TO EXIT" | |
S-1: |
Line One Selection. Sets the variable to be displayed on the top line of the display while in the Setup Select mode. Available: |
|
TIME |
||
S-2: |
Set Time Minutes. To adjust the minutes portion of the Real Time Clock. | |
S-3: |
Set Time Hours. To adjust the hours portion of the Real Time Clock. | |
S-4: |
Set Date Day. To adjust the day portion of the date display. | |
S-5: |
Set Date Month. To adjust the month. | |
S-6: |
Set Date Year. To adjust the year. | |
S-7: |
Set Day of Week. Adjusts day of week Sunday through Saturday. Day advances with date. | |
| -------- | S-8: |
SPEED CALIB: This setting is used to calibrate the speed signal so that the unit will display engine RPM. This setting must be adjusted for items such as crank stop RPM and OVERSPEED RPM to work. Simply enter the number of Pulses per revolution the magnetic pickup or alternator supplies to the unit . Another way to set this variable is to get the engine running at a known RPM and then change the number until the top line matches your known RPM. The resulting number is the pulses per revolution. Factory set to 6. |
| -------- | S-9: |
OVERSPEED: This setting allows you to enter the highest speed the engine can run before damage is caused. If the unit senses that the engine has exceeded this speed, it will signal the engine to shutdown. Factory set to 3200. |
| -------- | S-10: |
UNDERSPEED: If the engine speed dips to the RPM in this set-point, an automatic shutdown will be initiated. If you do not want to use this feature, change this variable to 0. Factory set to 2000. |
| -------- | S-11: |
LOCKOUT DELAY: This delay is used to ignore conditions such as low oil pressure when the engine first starts to allow the pressure time to reach its normal operating range (adjustable from 2 to 2,000 seconds). Factory set to 10. |
| -------- | S-12: |
LOP @ LOW SPD: The EMS Controller gives you two oil pressure shutdown points. For engines that develop very little oil pressure at an idle, you put a lower shutdown setting in this set-point. The unit automatically changes the shutdown point between the Low Speed Shutdown point and the High Speed Shutdown point. Factory set to 5. |
| -------- | S-13: |
LOP @ HI SPD: This set-point is the higher oil pressure shutdown point that is referred to in number 12 above. This is the point that you want the engine to shutdown during normal high speed engine operation. By shutting down the engine at a higher oil pressure, you can avert damage that could be caused by waiting to shut down the engine at the lower set-point needed to accommodate an idle. Factory set to 10. |
| -------- | S-14: |
LOP LO SPEED: Set this to your engine idle speed. If the engine is running at this speed, an idle for example, and the oil pressure reaches the set-point selected in S12, the unit will initiate an automatic shutdown. Factory set to 100. |
| -------- | S-15: |
LOP HI SPEED: Set this to your engine maximum speed. If the engine is running at this speed, and the oil pressure reaches the set-point selected in S13, the unit will initiate an automatic shutdown. Factory set to 600.
The Graph above shows how the set-point changes between your high speed set-point and low speed set-point. As the engine speed increases, the unit automatically raises the oil pressure shutdown set-point along a straight line between the two set-points you entered. This graph represents the following set-points: S12 is set to 10, S13 is set to 45, S14 is set to 600, and S15 is set to 2400. |
| -------- | S-16: |
HI ENG TEMP: Adjust this setting to the engine temperature you do not want to exceed. If the unit senses a coolant temperature higher than this set-point, it will initiate an automatic shutdown. Factory set to 320. |
| -------- | S-17: |
WARMUP DLY: You can adjust this variable to the number of seconds you want your engine to warmup before it engages the clutch and throttles up to an at load condition (adjustable from 1 to 300 seconds). Factory set to 5. |
| -------- | S-18: |
COOLDOWN DLY: You can adjust this variable to the number of seconds you wish to cool down your engine before it shuts off after a stop signal is received (adjustable from 1 to 300 seconds). Factory set to 5. |
| -------- | S-19: |
VENT FAN DLY: This delay adjustment determines how long the vent fan will be on before the cranking sequence begins (adjustable from 1 to 300 seconds). Factory set to 5. |
| -------- | S-20: |
ENG STRT DLY: Set this delay on engine start to the number of seconds that the start signal must be present before the unit accepts it and initiates an auto start sequence (adjustable from 1 to 300 seconds). Factory set to 2. |
| -------- | S-21: |
ENG STOP DLY: Set this delay on engine stop to the number of seconds that the stop signal must be present before the unit accepts it and initiates a stop sequence (adjustable from 1 to 300 seconds). Factory set to 2. |
| -------- | S-22: |
CRANK TIME: Set this delay to the desired amount of time you want each engine cranking attempt to last. Consult your engine manual for recommended cranking and resting times (adjustable from 1 to 300 seconds). Factory set to 10. |
| -------- | S-23: |
REST TIME: Set this delay to the desired amount of time you want each rest period between cranking attempts to last. Consult your engine manual for recommended resting and cranking times (adjustable from 1 to 300 seconds). Factory set to 10. |
| -------- | S-24: |
RECRANK DLY: This delay is used to adjust the amount of time the unit will wait for the engine to stop moving before attempting another crank if a false start occurs. A false start is when the engine starts but then dies before the LOCKOUT DELAY has expired (adjustable from 1 to 300 seconds). Factory set to 5. |
| -------- | S-25: |
CRK STOP RPM: This RPM set-point is used to adjust where the unit releases the starter during cranking. Set this to the RPM the engine attains just as it starts. This way, the starter is not engaged unnecessarily after the engine starts. You must also set this set-point to the speed you release the starter while cranking. This is how the unit senses whether the engine is running or not. You will get a NO SPEED SIGNAL shutdown if this is adjusted to high. Factory set to 250. |
| -------- | S-26: |
CRK ATTEMPTS: Set the number of attempts you would like the controller to try an engine start. If the engine fails to start after the number of attempts you have selected, it will fail the engine and display OVERCRANK on the front display. This shutdown requires a manual reset. Factory set to 6. |
| -------- | S-27: |
SPARE 1 TYPE: This set-point lets you pick the way you want the controller to handle an input on the spare 1 terminal. Your choices include: Immediate alarm only, Immediate alarm & Shutdown, Immediate alarm before shutdown, Delay alarm only, Delay alarm & shutdown, and Delay alarm before shutdown. These types of shutdowns are self explanatory. An immediate type alarm, shutdown or both will be processed whenever the input is active. A delay type alarm, shutdown or both will be processed after the Lockout Delay has expired (S5). Factory set to DELAY ALARM AND SHUTDOWN. |
| -------- | S-28: |
CHANGE OIL: Set the interval in engine running hours you wish to be prompted to change your engine oil. Factory set to 100. |
| -------- | S-29: |
CHG OIL FLTR: Set the interval in engine running hours you wish to be prompted to change your engine oil filter. Factory set to 200. |
| -------- | S-30: |
CHG FUEL FLT: Set the interval in engine running hours you wish to be prompted to change your engine fuel filter. Factory set to 1000. |
| -------- | S-31: |
SERV AIR CLN: Set the interval in engine running hours you wish to be prompted to service your engine air cleaner. Factory set to 200. |
| -------- | S-32: |
SERV BATTERY: Set the interval in engine running hours you wish to be prompted to service your cranking battery. Factory set to 200. NOTE: After service reminder time values have been set, the new values will not take effect (become active) until they have also been acknowledged in the P-Numbers below. |
| -------- | S-33: |
START VDC: Set this to the voltage the batteries being charged must drop to for the controller to initiate an auto start. Factory set to 48.5. |
| -------- | S-34: |
STOP VDC: Set this to the voltage the batteries being charged must rise to for the controller to initiate an auto stop. Factory set to 52.5. |
| -------- | S-35: |
MIN VDC: This set-point allows the configuration of the voltage divider analog input. The value entered here represents 0 vdc from the transmitter. Factory set to 0. |
| -------- | S-36: |
MAX VDC: This set-point allows the configuration of the voltage divider analog input. The value entered here represents 5 vdc from the transmitter. Adjustable from 0.0 to 1000.0. Factory set to 60.0. |
| -------- | S-37: |
BT VLT SLOPE: With the minimum amount of voltage present on your voltage transmitter, make this value match the number on the top line. Factory set to 0. |
| -------- | S-38: |
MAX AMPS: Set this to the value the current transmitter represents at 5 vdc. For example, if the current transmitter represents 0 - 100 amps, place 100 in this set point. Adjustable from 0 to 1000. Factory set to 870. |
| -------- | S-39: |
STOP AMPS: Set this to the value the charging current must fall below for the controller to initiate an auto stop. Factory set to 30. |
| -------- | S-40: |
AMPS SLOPE: With no current present on the current transmitter, make this value match the number on the top line. Factory set to 0. |
| -------- | S-41: |
FUEL PRS MAX: Set this to the value the fuel pressure transmitter represents at 5 vdc. For example, if the fuel pressure transmitter represents 0 - 100 PSI, place 100 in this set point. Adjustable form 0 to 500 PSI. Factory set to 250. |
| -------- | S-42: |
FUEL PRS SLP: With no fuel pressure present on the transmitter, make this value match the number on the top line. Factory set to 0. |
| -------- | S-43: |
LO FUEL PRS: When the fuel pressure drops below this set point the unit will display a LOW FUEL PRESSURE alarm and turn on the COMMON FAIL output. Factory set to 5. |
| -------- | S-44: |
AMB TP START: When the temperature rises to this set point the unit will start the COOLING OVERRIDE sequence. Factory set to 82. |
| -------- | S-45: |
AMB TP STOP: When the temperature falls below this set point the unit will stop the COOLING OVERRIDE sequence. Factory set to 72. |
| -------- | S-46: |
TEMP STRT DLY: Set this delay on start to the number of minutes that the start signal must be present before the unit accepts it and initiates a COOLING OVERRIDE start sequence (adjustable from 60 to 1,200 seconds). Factory set to 300. |
| -------- | S-47: |
TEMP STOP DLY: Set this delay on stop to the number of minutes that the stop signal must be present before the unit accepts it and initiates a COOLING OVERRIDE stop sequence (adjustable from 60 to 1,200 seconds). Factory set to 300. |
| -------- | S-48: |
HEATER START: When the engine block temperature drops below this set-point, the block heater circuit is activated. Factory set to 32. |
| -------- | S-49: |
HEATER DELTA: When the engine block temperature rises above the HEATER START temperature plus this set-point, the block heater circuit is de-activated. Factory set to 45. |
| -------- | 5-50: |
OIL P SELECT: Allows for the selection of the oil pressure type. The selections include SENDER or 0-5 VDC. Factory set to 0-5 VDC. |
| -------- | S-51: |
OIL PRS MAX: If the OIL P SELECT is set to 0-5 VDC then the controller uses the value entered here to calibrate what the maximum display for the oil pressure transducer represents. For example, if the oil pressure transmitter represents 0 - 100 PSI, place 100 in this set point. Factory set to 250. |
S-52: |
PF EOFF ENBL: This set point is used to enable or disable the vent operation when the engine is not running. If "YES" is selected then the controller will turn on the purge fan to regulate the temperature in the engine chamber. If "NO" is selected then the feature is disabled. Factory set to YES. | |
| -------- | S-53: |
A T FAN STOP: If the PF EOFF ENBL is set to "YES" then the controller will us the value set in this set point to start the vent fan when the engine is off. Factory set to 70° . |
| -------- | S-54: |
A T FAN STOP: If the PF EOFF ENBL is set to "YES" then the controller will us the value set in this set point to stop the vent fan when the engine is off. Factory set to 68° . |
| -------- | 5-55: |
ENGINE T SELECT: Allows for the selection of the display of the engine temperature type. The selections are OIL TEMP or H2O TEMP. Factory set to OIL TEMP. |
| -------- | S-56: |
MODEM SETUP: Enables or disables the modem communications. The selections are NONE for no modem connected. REC ONLY for the modem to receive only. XMIT ONLY for the modem to transmit only. And XMIT/REC for transmit and receive. |
| -------- | S-57: |
CALL ATTMPTS: This sets the total times the controller will attempt to dial the three (3) phone numbers. |
| -------- | S-58: |
CALL LENGTH: This sets the total length in time the controller will stay connected to the remote terminal (adjustable from 20 to 9,999 seconds). |
| -------- | S-59: |
1ST CALL #: This sets 1st number the controller will attempt to call. |
| -------- | S-60: |
2ND CALL #: If the 1st number fails to connect, this sets the 2nd number the controller will attempt to call. |
| -------- | S-61: | 3RD CALL #: If the 1st and 2nd number fails to connect, this sets the 3rd number the controller will attempt to call. |
| -------- | S-62: | MOD RETRY DLY: If the controller does not connect to the remote terminal with the three calls, this sets the time interval between the next cycle of calls (adjustable from 60 to 999 seconds). Factory set to 120. |
| -------- | S-63: | PASSWORD: This sets the password required by the remote terminal. |
| -------- | S-64: | CNTRLR NAME: This sets the name the controller will use to log on to the remote terminal. |
| -------- | S-65: | MODEM BAUD: This sets the baud rate the controller will use to connect to the remote terminal. Adjustable from 1200 to 9600 bps. |
| -------- | S-66: | MODEM INIT 1: Allows the programming of the initialization string to the modem. |
| -------- | S-67: | MODEM INIT 2: If more room is needed for the programming of the initialization string to the modem use this set-point. |
| -------- | S-68: | MODEM TYPE: Use this to set-up the type of modem. The choices are OTHER, ZOOM 14.4 and AT&T DP 14.4. If other is selected then the controller will look to the programmable init string S#s for the initialization string of the modem. |
| -------- | S-69: | M INIT UPDTE: When the set-up of the modem is complete, use this set-point to force the controller to accept the new initialization string. |
| Accessing the P-Numbers The EMS Controller has P-numbers in addition to the S-numbers you configured in the previous step. These are accessed in the same manner but using a different access code. See the Secret Code Supplement for this code number. |
P.0: |
Manual 'EXIT' from the S-number setup mode. Press " 'CIRCLE' TO EXIT" |
P.1: |
Line One Selection. Sets the variable to be displayed on the top line of the display while in the Setup Select mode. Available: |
| TIME DATE |
|
P.2: |
VDC @ SHDW: Shows what the charging battery voltage was when the unit initiated the last failure shutdown. To view the information, press the l button. |
P.3: |
VDC @ SHDW: Shows what the charging battery voltage was when the unit initiated the last failure shutdown. To view the information, press the l button. |
P.4: |
OIL PR @ SHDW: Shows what the engine oil pressure was when the unit initiated the last failure shutdown. To view the information, press the l button. |
P.5: |
TEMP @ SHDWN: Shows what the engine temperature was when the unit initiated the last failure shutdown. To view the information, press the l button. |
P.6: |
TACH @ SHDWN: Shows what the engine speed was when the unit initiated the last failure shutdown. To view the information, press the l button. |
P.7: |
FUEL PRS @ SD: Shows what the fuel pressure was when the unit initiated the last failure shutdown. To view the information, press the l button. |
P.8: |
LAST SHUTDOWN: Shows what caused the last failure shutdown and the time in running hours that it occurred. To view the information, press the l button. |
P.9-17: |
##th SHUTDWN: These P-numbers store the 2nd through the 10th cause of failure shutdown and the running hours they occurred. To view the information, press the l button. |
P.18: |
ACK CHG OIL: This setting allows the user to acknowledge that he/she has changed the oil in the engine as prompted by the unit. When this setting is toggled from NO to YES, the unit resets the counter and will not prompt the user again until the selected number of running hours has elapsed. |
P.19: |
ACK OIL FLTR: This setting allows the user to acknowledge that he/she has changed the oil filter as prompted by the unit. When this setting is toggled from NO to YES, the unit resets the counter and will not prompt the user again until the selected number of running hours has elapsed. |
P.20: |
ACK FUEL FLT: This setting allows the user to acknowledge that he/she has changed the fuel filter as prompted by the unit. When this setting is toggled from NO to YES, the unit resets the counter and will not prompt the user again until the selected number of running hours has elapsed. |
P.21: |
ACK AIR CLNR: This setting allows the user to acknowledge that he/she has changed or serviced the air cleaner as prompted by the unit. When this setting is toggled from NO to YES, the unit resets the counter and will not prompt the user again until the selected number of running hours has elapsed. |
P.22: |
ACK BATTERY: This setting allows the user to acknowledge that he/she has serviced / changed the battery as prompted by the unit. When this setting is toggled from NO to YES, the unit resets the counter and will not prompt the user again until the selected number of running hours has elapsed. |
P.23: |
PROGRAM #: The value in this window is the program and version number. This is helpful information to have before calling our office for help. |
| General Wiring Precautions There are several precautions you can take on initial installation to reduce chances of failure over time. Many of these steps may take a few extra minutes to do at the time of installation; however, they can also save many headaches in the future. We strongly recommend that you follow these precautionary steps. |
Remember, proper care during installation will help your EMS Controller live a long and trouble-free operating life. If for any reason you have questions during installation, feel free to give us a call. |
| Double Checking Your Wiring The EMS Controller has built in diagnostic information for confirming your wiring before you attempt to auto start your engine. The diagnostic information is found in the S-numbers under S1 LINE 1 SELECT. The factory default line 1 display shows the engine RPM. By scrolling through the displays, you will see the
following: |
|
This represents the 4 standard digital only inputs. An O means that the input is not active. An X means that the input is active.
The next screen shows the rest of your inputs: |
|
The next screen shows the state of your outputs: |
|
|
| Port Connection Description The EMS547 controller has four (4) DB connectors on the back. The following is a description of the ports. UNLESS OTHERWISE SPECIFIED THE FOLLOWING FEATURES MAY NOT BE AVAILABLE IN THIS APPLICATION. Refer to the Additional Features Section above.
|
|
PIN |
HARDWARE ASSIGNMENT |
PROGRAM PIN ASSIGNMENT |
1 |
Analog 4 |
Ambient Temperature (0-5vdc) |
2 |
Analog 0 |
Battery Monitor ( No customer hookup) |
3 |
Analog 7 |
Fuel Pressure Input (0-5vdc) |
4 |
Analog 1 |
Electric gauge Water Temperature Sender |
5 |
Input 1 |
Auto Position of Test Off Auto Toggle Switch |
6 |
Input 2 |
Test Position of Test Off Auto Toggle Switch |
7 |
Output 1 |
Fuel Solenoid Output |
8 |
Battery + |
Battery Plus |
9 |
Battery + |
Battery Plus |
10 |
Output 2 |
Starter Output |
11 |
Battery - |
Ground |
12 |
Output 3 |
Common Fail Output |
13 |
Frequency Input |
Frequency Input |
14 |
Analog 6 |
Battery Voltage input (0-5vdc) |
15 |
Analog 5 |
Charging Current (0-5vdc) |
16 |
Analog 3 |
Low Coolant Level Input (Closed on Fault) |
17 |
Analog 2 |
Electric Gauge Sender for Engine Oil Pressure |
18 |
Input 3 |
Spare 1 Input (Shutdown / Alarm) |
19 |
Input 4 |
Remote Start/Stop |
20 |
Output 4 |
Block Heater Control |
21 |
Output 5 |
Chiller control |
22 |
Output 6 |
Exhaust Vent Control |
23 |
Output 7 |
Generator Regulator Control |
24 |
RS485 - |
RS485 (-) |
25 |
RS485 + |
RS485(+) |
|
Pin # |
|
Pin # |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pin # |
|
Pin # |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pin # |
|
Pin # |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Entry Code
SupplementWARNING
Knowledge of these codes allows you to set the operating parameters of the controller. You can customize the operation to fit your specific application. Keep this number away from anyone that you do not want to have access to this kind of customization. P-NUMBERSThe P-numbers contain less critical engine operating parameters. You will find the ability to acknowledge service reminders. The shutdown history is also stored here. The entry code number is 61. S-NUMBERSThe S-numbers contains critical information and control functions. Items that are set improperly in the S-Numbers can cause serious operation problems. Be sure that only qualified personal have access to this entry code. The entry code number is 64. |
I / O LIST FOR 40-94-115 PROGRAM.
Port #1 User Interface
PIN |
S449 |
HARDWARE ASSIGNMENT |
PROGRAM PIN ASSIGNMENT |
| 1 | 31 | Analog 4 |
Thermostat Temperature (o-5vdc) |
| 2 | 33 | Analog 0 |
Battery Monitor ( No customer hookup) |
| 3 | 35 | Analog 7 |
Fuel Pressure Input (0-5vdc) |
| 4 | 37 | Analog 1 |
Electric gauge Water Temperature Sender |
| 5 | 39 | Input 1 |
Auto Position of Test Off Auto Toggle Switch |
| 6 | 11 | Input 2 |
Test Position of Test Off Auto Toggle Switch |
| 7 | (K6) 7, 8, 16, 17, 18, 19 | Output 1 |
Fuel Solenoid Output |
| 8 | 20 | Battery + |
Battery Plus |
| 9 | 20 | Battery + |
Battery Plus |
| 10 | (K2) 4,5,6, and 13, 14, 15 | Output 2 |
Starter Output |
| 11 | 9, 10 | Battery - |
Ground |
| 12 | (K1) 21, 22 | Output 3 |
Common Fail Output |
| 13 | 1 | Frequency Input |
Frequency Input |
| 14 | 32 | Analog 6 |
Battery Voltage input (0-5vdc) |
| 15 | 34 | Analog 5 |
Charging Current (0-5vdc) |
| 16 | 36 | Analog 3 |
Low Coolant Level Input (Closed on Fault) |
| 17 | 38 | Analog 2 |
Electric Gauge Sender for Engine Oil Pressure |
| 18 | 40 | Input 3 |
Spare 1 Input (Shutdown / Alarm) |
| 19 | 12 | Input 4 |
Remote Start/Stop |
| 20 | (K3) 23, 24 | Output 4 |
Block Heater Control |
| 21 | (K4) 25, 26 | Output 5 |
Chiller control |
| 22 | (K5) 27, 28 | Output 6 |
Exhaust Vent Control |
| 23 | (K7) 29, 30 | Output 7 |
Generator Regulator Control |
| 24 | 3 | RS485 - |
RS485 (-) |
| 25 | 2 | RS485 + |
RS485(+) |